On this page
- 01What are the main parts of a cold room?
- 02How does a cold room keep its temperature?
- 03What temperature does each type of cold room run at?
- 04What is the difference between walk-in, modular and built-in-place cold rooms?
- 05Where are cold rooms used in India?
- 06How is a cold room sized?
- 07How much does a cold room cost?
- 08What should you check before buying a cold room in India?
- FAQFrequently asked questions
Quick answer
A cold room is an insulated, refrigerated room that holds a set temperature, from about +20 °C for ripening down to −40 °C for blast freezing, to store perishable or temperature-sensitive goods. It has four parts: a PUF panel envelope (80–150 mm thick), an insulated door, a refrigeration system (condensing unit plus evaporator) and a controller.
Key takeaways
- A cold room has four parts: a PUF panel envelope, an insulated door, a refrigeration system (condensing unit plus evaporator) and a controller.
- HyperCold's configurator uses 80 mm panels for +8 to +15 °C rooms, 100 mm for 0 to +8 °C, 120 mm for −18 to −22 °C and 150 mm for deep-freeze and blast rooms.
- Capacity in MT is gross volume × usable fraction × as-stacked density ÷ 1,000, so an 8 × 8 × 8 ft chiller holds about 5.2 MT.
- Refrigeration is sized on heat load at a 45 °C design ambient with a 10% safety margin, not on floor area.
- Rooms wider than 10 ft need an MS iron roof support structure because PUF roof panels self-span only about 10 ft.
What are the main parts of a cold room?
Every cold room, from an 8 × 8 ft restaurant chiller to a multi-room pack-house, is built from the same four systems. What changes with temperature is the thickness of the envelope and the series of the refrigeration machine.
- Insulated envelope — walls, ceiling and floor made from PPGL (pre-painted galvalume) sheet-skinned PUF panels. HyperCold's configurator uses 80 mm panels for +8 to +15 °C rooms, 100 mm for 0 to +8 °C, 120 mm for −18 to −25 °C and 150 mm for deep-freeze and blast rooms (−25 to −40 °C). Foam density is specified at 40 ± 2 kg/m³.
- Insulated door — a hinged or sliding door of the same thickness as the walls, with a compression gasket, and a door heater on freezer rooms so the seal does not freeze shut.
- Refrigeration system — a condensing unit outside the room (compressor, condenser coil and fan) and an evaporator or unit cooler inside (coil, fans and electric defrost), joined by insulated refrigerant piping.
- Controller — holds the set point and manages defrost. HyperCold's standard option is a basic thermostat controller with manual defrost; the premium IoT HMI adds app-based remote monitoring, SMS alerts and data logging.
Around these sit the accessories that decide real-world performance: PVC strip curtains, an ante room for high-traffic doors, drain lines, lighting and, for sub-zero rooms, an insulated floor with a vapour barrier.
How does a cold room keep its temperature?
A cold room does not make cold; it removes heat. The evaporator fans pull room air across a coil of evaporating refrigerant, the compressor pumps that heat outside, and the condenser rejects it to the ambient air. The insulation's job is to slow down how fast heat leaks back in.
Heat enters from five places, and the machine has to remove all of them on the hottest day of the year:
- Transmission through walls, ceiling and floor. At a conductivity of about 0.022 W/m·K, a 100 mm PUF panel has a U-value of roughly 0.22 W/m²·K.
- Product load — field heat of warm product, plus respiration heat from fruit and vegetables, which are still alive.
- Infiltration — warm, humid air entering every time the door opens; in Indian retail and HoReCa rooms this is usually the biggest load.
- Internal loads — people, lights, trolleys or forklifts and the evaporator fans themselves.
- Defrost — heat added to melt frost off the coil.
Indian design has to assume a 45 °C summer ambient, which is the default design ambient in HyperCold's heat load calculator. A machine selected for a mild day will run non-stop and still drift off set point in May and June.
What temperature does each type of cold room run at?
HyperCold's quotation configurator lists the room types below. The temperature band decides the panel thickness and the refrigeration series, which is why a freezer costs far more than a chiller of the same size.
| Room type | Temperature | Humidity | Default panel | Typical use |
|---|---|---|---|---|
| Fruits & vegetables | 0 to +15 °C (by commodity) | 85–95% | 80 mm | Fresh produce, FPO and trader stores |
| Ripening chamber | +14 to +20 °C | 90–95% | 80 mm | Banana and mango ripening |
| Chiller | 0 to +8 °C | 80–90% | 100 mm | Dairy, beverages, packed food |
| Fresh meat chiller | −1 to +2 °C | 85–95% | 100 mm | Fresh meat and poultry |
| Pharmaceutical | +2 to +8 °C | 60–70% | 100 mm | Medicines and vaccines |
| Egg room | +4 to +8 °C | 75–85% | 100 mm | Layer farms, egg traders, hatcheries |
| Floriculture | +2 to +6 °C | 90–95% | 100 mm | Cut flowers and bouquets |
| Frozen storage | −18 to −22 °C | 90–95% | 120 mm | Frozen food and ice cream |
| Deep freezer | −25 to −30 °C | 90–95% | 150 mm | Seafood and specialty items |
| Blast freezer | −35 to −40 °C | 85–90% | 150 mm | Rapid freezing before storage |
| Ante room | +10 to +15 °C | 70–80% | 80 mm | Buffer between ambient and cold room |
Set points inside the fruit-and-vegetable band vary widely — potato, onion, apple and banana each need a different temperature and humidity — so check the cold storage temperature chart before fixing the set point. A blast freezer is a process room: it freezes a batch and hands it to a frozen store; it never holds stock.
What is the difference between walk-in, modular and built-in-place cold rooms?
These three terms describe different things, which is why buyers mix them up.
- Walk-in describes access and size: a room people walk into, as opposed to a reach-in cabinet or chest freezer. HyperCold's walk-ins start at about 5 MT.
- Modular describes construction: factory-foamed PUF panels locked together on site with cam-locks, on a levelled floor inside a shed or building. HyperCold's walk-ins are modular.
- Built-in-place also describes construction: insulation applied to masonry or RCC walls built on site, as in some bulk cold storages.
| Factor | Modular PUF panel room | Built-in-place room |
|---|---|---|
| Build time | Delivery 2–4 weeks from order confirmation | Civil work and curing first, then insulation |
| Insulation quality | Factory-foamed, uniform thickness and density | Depends on site workmanship |
| Relocation or expansion | Panels can be dismantled, reused or extended | Fixed; expansion means new civil work |
| Best fit | About 5 MT to a few hundred MT | Very large stores built with the building |
One structural rule from HyperCold's configurator: PUF roof panels self-span only about 10 ft, so any room wider than 10 ft gets an MS iron roof support structure (priced extra), and standard designs stop at 20 ft internal width.
Where are cold rooms used in India?
Cold rooms sit at every point in the Indian cold chain where product has to wait — after harvest, before sale, between processing batches.
- Hotels, restaurants and cloud kitchens — +2 to +4 °C chillers for dairy, meat and vegetables, often with a small −18 °C freezer.
- Farmers, FPOs and traders — produce rooms at 0 to +15 °C depending on the crop, usually next to grading or a pack-house.
- Banana and mango ripeners — ripening chambers at +14 to +20 °C with ethylene gas; FSSAI prohibits calcium carbide.
- Dairies and sweet shops — +2 to +5 °C for milk, curd and paneer; −18 to −22 °C for ice cream.
- Meat, fish and poultry — −1 to +2 °C fresh chillers, blast freezers, and −25 °C or colder deep freezers for export seafood.
- Pharma distributors and hospitals — +2 to +8 °C rooms with temperature mapping, alarms and 24 × 7 logging.
- Florists, egg traders and hatcheries — +2 to +6 °C flower rooms and +4 to +8 °C egg rooms.
Above a few hundred MT the job usually moves from a cold room to a multi-chamber cold storage, with different construction, refrigeration and subsidy rules.
How is a cold room sized?
Sizing has two separate answers: how much product fits (storage capacity in MT) and how much refrigeration is needed (heat load in kW or TR).
Capacity comes from volume, not floor area. HyperCold's configurator uses capacity (MT) = gross volume (m³) × usable fraction × as-stacked bulk density (kg/m³) ÷ 1,000. For a chiller holding racked cartons that is 0.65 × 550 kg/m³, so an 8 × 8 × 8 ft room (14.5 m³) holds about 5.2 MT. The full method, with room sizes for 5, 10 and 20 MT, is in how to calculate cold room capacity.
Refrigeration comes from the heat load: transmission at 45 °C ambient, daily loading and pull-down, door openings and internal loads, plus a 10% safety margin. The heat load calculator shows the breakdown in kW and TR (1 TR ≈ 3.517 kW), and the quotation always picks the next-larger standard Daikin machine. If you do not know your numbers yet, the cold room calculator collects product, capacity, daily loading and site details for a sized recommendation.
How much does a cold room cost?
Price follows the same logic as the design: size sets the panel area, temperature sets panel thickness and machine series, and the site sets the extras. On HyperCold's FY2026-27 rate card (GST extra), an 8 × 8 × 8 ft chiller with 100 mm panels, a 2 HP Daikin unit and a standard controller comes to about ₹2.6 lakh plus GST in the configurator. A 10 × 8 × 8 ft freezer is about ₹4.6 lakh plus GST, because it needs 120 mm panels, a low-temperature machine and a standby unit.
Freight, civil work, flooring and the power connection are extra, and the final price follows a site survey. The quotation configurator prices any size, temperature and controller option instantly, with a line-item BOQ.
What should you check before buying a cold room in India?
- Design ambient — ask which ambient the machine was selected for; 45 °C is the realistic north and central India summer figure.
- Power and backup — confirm the connected load, protect the compressor against voltage dips and DG changeover, and decide whether a DG or UPS must carry the room (a backup power system is ₹1,26,000 on HyperCold's rate card, GST extra).
- Floor — rooms below 0 °C need an insulated floor with a vapour barrier; deep-freeze rooms also need under-floor heating to prevent frost heave.
- Door discipline — a PVC strip curtain (₹8,925 per door on the rate card) and an ante room protect set point more cheaply than extra insulation.
- Standby — HyperCold's configurator pairs every frozen room with a standby condensing unit, so one breakdown does not cost the stock.
- Scope — civil work, foundation, flooring, drainage, power connection and freight are normally client scope; get them written into the quotation.
FAQ
Frequently asked questions
Is a chiller room the same as a cold room?
A chiller room is one type of cold room, held at 0 to +8 °C for dairy, beverages and packed food. 'Cold room' is the umbrella term that also covers freezer rooms (−18 to −22 °C), ripening chambers, pharma rooms and blast freezers.
What is the difference between a cold room and a deep freezer?
A deep freezer is a self-contained chest or upright cabinet with a built-in compressor, sized in litres. A cold room is a walk-in insulated room with a separate condensing unit and evaporator, sized in MT, and can run at chiller or freezer temperatures.
How long does a PUF panel cold room last?
A well-built PUF panel cold room with planned maintenance runs 15–20 years, and the panels usually outlast the first refrigeration overhaul. HyperCold's quotation lists a 7-year manufacturer warranty on PPGL PUF panels and 3 years on the Daikin compressor.
Can a cold room be installed inside an existing building?
Yes. A modular PUF panel room is erected on a levelled floor inside a shed or godown, with the condensing unit placed outside where it can reject heat. Rooms wider than 10 ft also need an MS roof support structure.
What is an ante room?
An ante room is a +10 to +15 °C buffer chamber in front of the cold room door. It is not rated for storage; it cuts the heat and moisture entering the main room and stops cold cartons sweating on the way out.
Written by
HyperCold Engineering Team
Cold room and cold storage engineers at HyperCold™, a Daikin equipment partner founded in 2020 and headquartered in Sirsaganj, Firozabad (UP). We design, manufacture PUF panels for, install and maintain cold rooms across India.